Lines Matching full:polling
6 such as trip points, polling intervals, sensors and cooling devices
129 - polling-delay: The maximum number of milliseconds to wait between polls
133 - polling-delay-passive: The maximum number of milliseconds to wait
170 (i) - when passive cooling is activated (polling-delay-passive); and
171 (ii) - when the zone just needs to be monitored (polling-delay) or
177 between polls. Choosing the right polling delays shall avoid having the
249 polling-delay-passive = <250>; /* milliseconds */
250 polling-delay = <1000>; /* milliseconds */
322 polling-delay-passive = <250>; /* milliseconds */
323 polling-delay = <1000>; /* milliseconds */
349 polling-delay-passive = <120>; /* milliseconds */
350 polling-delay = <1000>; /* milliseconds */
376 polling-delay-passive = <50>; /* milliseconds */
377 polling-delay = <1000>; /* milliseconds */
450 polling-delay-passive = <250>; /* milliseconds */
451 polling-delay = <1000>; /* milliseconds */
508 polling-delay-passive = <500>; /* milliseconds */
509 polling-delay = <2500>; /* milliseconds */
524 polling-delay-passive = <1000>; /* milliseconds */
525 polling-delay = <2500>; /* milliseconds */